VU120 - Classification

Classification Scroll down/right to view the entire table

File Type Material Sealing Classification
Download Duct Promatect L500 ≥ 30 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Geoflam ≥ 30 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Geotec ≥ 30 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Tecniver ≥ 35 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Glasroc F V500 ≥ 35 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Exthamat ≥ 25 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Desenfire HD ≥ 25 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 60 (ved hod i o) S 1500 AA multi
Download Duct Promatect L500 ≥ 40 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 90 (ved hod i o) S 1500 AA multi
Download Duct Geoflam ≥ 35 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 90 (ved hod i o) S 1500 AA multi
Download Duct Tecniver ≥ 45 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 90 (ved hod i o) S 1500 AA multi
Download Duct Exthamat ≥ 30 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 90 (ved hod i o) S 1500 AA multi
Duct Desenfire THD ≥ 25 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 90 (ved hod i o) S 1500 AA multi
Download Shaft Reinforced concrete (≥ 2150 kg/m³) ≥ 70 mm Mortar EI 90 (ved i o) S 1500 AA multi
Download Duct Promatect L500 ≥ 50 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Geoflam ≥ 45 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Geoflam Light ≥ 35 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Geotec ≥ 45 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Tecniver ≥ 50 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Glasroc F V500 ≥ 50 mm Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Exthamat ≥ 35 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Duct Desenfire HD ≥ 35 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Duct Desenfire STR ≥ 25 mm Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) EI 120 (ved hod i o) S 1500 AA multi
Download Shaft Masonry, concrete blocks, concrete ≥ 100 mm Mortar EI 120 (ved i o) S 1500 AA multi

Installation

# Installation