GE90 - Installation

Installation in rigid wall

The product was tested and approved in:
  • Aerated concrete ≥ 100 mm | EI 90 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 ≤ GE90 ≤ 800x400 mm
  • Aerated concrete ≥ 100 mm | EW 90 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 ≤ GE90 ≤ 800x400 mm
1
Provide a min. installation opening in the wall = Wn x Hn.
Apply BCM sealing glue on all sides of the grill.
2
Mount the grill in the wall.
The product must be installed with the lamellas in their horizontal position.

General remarks

  • The installation must comply with the installation manual and the classification report.
  • Rf-t fire resistant grills are always tested in standardised constructions according to EN 1634-1/EN 1364-1/EN 1364-2. The achieved results are valid for similar supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used during the test.