GE90 - Installation
Installation in rigid wall
The product was tested and approved in:
- Aerated concrete ≥ 100 mm | EI 90 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 ≤ GE90 ≤ 800x400 mm
- Aerated concrete ≥ 100 mm | EW 90 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 ≤ GE90 ≤ 800x400 mm
General remarks
- The installation must comply with the installation manual and the classification report.
- Rf-t fire resistant grills are always tested in standardised constructions according to EN 1634-1/EN 1364-1/EN 1364-2. The achieved results are valid for similar supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used during the test.