- Home
- Products
- Fire resistant grills
- GE60
- Installation
GE60 - Installation
Installation in rigid wall
The product was tested and approved in:
- Aerated concrete ≥ 100 mm | EI 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GE60 ≤ 800x400 mm
- Aerated concrete ≥ 100 mm | EW 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GE60 ≤ 800x400 mm
Provide a min. installation opening in the wall = Wn x Hn.
Apply BCM sealing glue on all sides of the grill.
Apply BCM sealing glue on all sides of the grill.
Mount the grill in the wall.
The product must be installed with the lamellas in their horizontal position.
The product must be installed with the lamellas in their horizontal position.
General remarks
- The installation must comply with the installation manual and the classification report.
- Rf-t fire resistant grills are always tested in standardised constructions according to EN 1634-1/EN 1364-1/EN 1364-2. The achieved results are valid for similar supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used during the test.