GZ60 - Installation
Installation in rigid wall
The product was tested and approved in:
- Aerated concrete ≥ 100 mm | EI 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm
- Aerated concrete ≥ 100 mm | EW 90 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm
Installation in rigid floor
The product was tested and approved in:
- Aerated concrete ≥ 100 mm | EI 60 (ho i o) | Not applicable | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm
- Aerated concrete ≥ 100 mm | EW 60 (ho i o) | Not applicable | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm
Installation in flexible wall (metal stud gypsum plasterboard wall)
The product was tested and approved in:
- Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm | EI 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm
- Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm | EW 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 800x400 mm

Attach two standard gypsum boards with a thickness of 12,5mm to one side of the metal stud wall.
Insulate with stonewool (min. 40kg/m³) and finish with two standard gypsum boards.
Insulate with stonewool (min. 40kg/m³) and finish with two standard gypsum boards.

Fix in the opening a frame in calcium silicate boards (with a thickness of 15mm) with standard mortar.
Installation in a wooden door panel
The product was tested and approved in:
- Wooden door panel ≥ 50 mm | EI 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 600x400 mm
- Wooden door panel ≥ 50 mm | EW 60 (ve i o) | Sealing glue BCM | Type of installation: built-in, sleeves horizontal | 100x100 mm ≤ GZ60 ≤ 600x400 mm
General remarks
- The installation must comply with the installation manual and the classification report.
- Rf-t fire resistant grills are always tested in standardised constructions according to EN 1634-1/EN 1364-1/EN 1364-2. The achieved results are valid for similar supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used during the test.