MG-U L150 - Installation
Installation in rigid wall and in flexible wall (metal stud gypsum plasterboard wall), without screws
The product was tested and approved in:
- see the classification overview.
- Mounting is authorised in supporting constructions with a thickness and/or density equal or superior to the supporting construction used during the test, as described in EN 1366-3.
Installation in rigid wall and in flexible wall (metal stud gypsum plasterboard wall), with screws
The product was tested and approved in:
- see the classification overview in the Declaration of Performance.
- Mounting is authorised in supporting constructions with a thickness and/or density equal or superior to the supporting construction used during the test, as described in EN 1366-3.

Provide an installation opening of minimum Ød + 27 mm and maximum Ød + 50 mm for pipe diameters 32-75, Ød + 36 mm and Ød + 50 mm for pipe diameters 80-110, Ød + 40 mm and Ød + 50 mm for pipe diameters 125-160.

Bend the collar and mount it around the pipe.
Slide the fastening strips through the corresponding holes.
Fold back the strips.
Slide the fastening strips through the corresponding holes.
Fold back the strips.
Installation in rigid floor, without screws
The product was tested and approved in:
- see the classification overview in the Declaration of Performance.
- Mounting is authorised in supporting constructions with a thickness and/or density equal or superior to the supporting construction used during the test, as described in EN 1366-3.
Installation in rigid floor, with screws
The product was tested and approved in:
- see the classification overview in the Declaration of Performance.
- Mounting is authorised in supporting constructions with a thickness and/or density equal or superior to the supporting construction used during the test, as described in EN 1366-3.
General remarks
- The installation must comply with the installation manual and the classification report.
- The pipe must be supported in order to guarantee the well-functioning of the sealing during a fire. Supports and fastenings should be realised according to the rules of good craftsmanship.
Product-specific remarks
- See our installation video at www.rft.eu/VIDEO-MG-U (or scan the QR code on cover of product brochure).